How it is worked out
- Harmonic current. The non-linear load current multiplied by its current distortion:
Ih = I × THDi ÷ 100. - What may remain. 5 % of the total load current at the supply is allowed to stay.
- Filter current. The difference, with a 20 % margin:
If = (Ih − allowed) × 1.2. - Modules. The smallest total from standard modules of 30 to 300 A, with up to six in parallel.
- CTs and losses. Sensing CTs are chosen for 1.2 times the larger of the load and the filter current. Losses are taken as 3 % of the filter rating.
A worked example
Drives draw 600 A with 40 % current distortion. The total load at the supply is 900 A.
Allowed at the supply = 5 % of 900 = 45 A
Filter current = (240 − 45) × 1.2 = 234 A
Modules = 4 × 60 A = 240 A
Sensing CTs = 3 nos 1200/5 A
Before you order
- Measure before you buy. An assumed distortion can be far from the real one.
- Leave room and air for the filter. It turns about 3 % of its rating into heat.
- If capacitors without reactors are on the same bus, deal with them first. They can resonate and overload the filter.
Questions people ask
Where do I get the THDi figure?
Best from a measurement at site with a power analyser. For a first estimate, a six-pulse drive with a line reactor or DC choke is often taken at 35 to 45 %. Without any choke it can be far higher, so do not guess low.
Why 5 % at the supply?
It is the target most specifications ask for at the point of supply. If your specification gives another limit, size the filter for that limit.
Where do the CTs go?
On the supply side or the load side of the filter connection, as the maker's manual says for the control mode chosen. In the PanelPro application the CT position is drawn.
Does an active filter also correct power factor?
Most can supply some reactive current as well, within their rating. Current used for power factor is not available for harmonics, so size for both if you want both.