Guide · panel design

APFC panel sizing: kVAr, steps and detuned reactors

An APFC panel is sized in four moves: how many kVAr, in what steps, with or without reactors, and through what switchgear. Each has one sum and one common mistake.

Move 1: How many kVAr

The kVAr needed depends on the running load and on the power factor before and after.

kVAr = kW × (tan φ1 − tan φ2)

You do not need a calculator for the tangents. Multiply the load in kW by the figure in this table.

Power factor nowTo reach 0.95To reach 0.98To reach 0.99To reach 1.00
0.700.6920.8170.8781.020
0.750.5530.6790.7390.882
0.800.4210.5470.6080.750
0.850.2910.4170.4770.620
0.900.1560.2810.3420.484

Worked example

Load 500 kW, power factor 0.80, target 0.98
kVAr = 500 × 0.547 = 273.5 kVAr → a 275 kVAr bank

Look at the last column. Going from 0.98 to 1.00 for the same load needs another 100 kVAr. That is why most plants stop at 0.98 or 0.99.

The common mistake: using the connected load of the plant in place of the running load. The bank comes out too large, and at light load the power factor goes leading.

Move 2: In what steps

The relay switches whole steps, so the smallest step sets how closely the bank can follow the load. A good pattern is 1 : 2 : 2: one small step and the rest twice its size.

275 kVAr = 1 × 25 + 5 × 50, six steps, six-stage relay
The bank can then settle at any multiple of 25 kVAr up to 275

More, smaller steps follow the load better but cost more in switchgear and take more space. Fewer, larger steps are cheaper and leave the power factor hunting between two values.

The common mistake: making every step large, for example 6 × 50 kVAr. At low load the relay has nothing small enough to switch.

Move 3: With reactors, and at what voltage

Capacitors and the supply transformer form a tuned circuit. If its resonance falls on a harmonic that drives produce, the harmonic current is amplified and capacitors fail. A detuned reactor in series with each step moves the resonance to a safe place.

7 % reactor at 50 Hz → resonance at 50 ÷ √0.07 = 189 Hz, below the 5th harmonic (250 Hz)

The reactor raises the voltage across the capacitor.

Capacitor voltage = 415 ÷ (1 − 0.07) = 446 V → use 480 V capacitors

A capacitor's kVAr is stated at its own rated voltage, so the capacitor for a step is not the same number as the step.

Capacitor rating = step kVAr × (1 − 0.07) × (480 ÷ 415)²
25 kVAr step → 31.1 kVAr at 480 V
50 kVAr step → 62.2 kVAr at 480 V

The common mistake: fitting 440 V capacitors of the step's own kVAr behind reactors. The capacitor runs above its voltage rating and the step delivers the wrong kVAr.

Move 4: Through what switchgear

Capacitor current = kVAr × 1000 ÷ (1.732 × 415)
275 kVAr → 383 A; incomer and busbar for 1.5 × = 574 A, so a 630 A incomer
  • Rating. Capacitors may draw more than their rated current, because of harmonics and tolerance. Switchgear, fuses and busbars are sized for about 1.5 times the capacitor current.
  • Contactors. Use capacitor-duty contactors, which limit the inrush when a step switches in.
  • Thyristor switching. For loads that change within seconds, such as welding, cranes or presses, contactors are too slow and thyristor modules are used.
  • Discharge. A step must not switch back in until it has discharged. Set the relay's reconnection time to suit the discharge resistors.
  • Heat. Reactors and capacitors give off heat. Provide ventilation and keep the capacitors away from the hottest part of the panel.

Check the result

The APFC kVAr calculator does these sums from the load and the two power factors. In the PanelPro application each step then gets its reactor, its contactor or thyristor module and its protection, and the resonance of the bank with your transformer is checked.

Figures here are for a 415 V, 50 Hz system. Confirm capacitor and reactor ratings with the maker's catalogue for the job.

Questions people ask

How do I calculate kVAr from kW and power factor?

kVAr = kW × (tan φ1 − tan φ2), where cos φ1 is the power factor now and cos φ2 the one you want. For 500 kW from 0.80 to 0.98 that is 500 × 0.547 = 273.5 kVAr.

What is a detuned reactor, and when do I need one?

It is a reactor in series with each capacitor step that moves the resonance of the bank below the lowest harmonic present. It is needed wherever drives, UPS systems or other non-linear loads share the supply, which is most plants today.

What does 7 % mean on a reactor?

The reactor's impedance is 7 % of the capacitor's at 50 Hz. The step then resonates at 189 Hz, safely below the fifth harmonic at 250 Hz.

Why do capacitors fail early?

The usual causes are heat, harmonics, switching back in before the capacitor has discharged, and a voltage rating too low for use behind a reactor.