BIRADAR PANELPRO
Calculator

APFC kVAr calculator

Type the load and the power factor now and wanted. The calculator gives the kVAr, the steps, the capacitor rating behind 7 % reactors and the incomer current.

Your figures

How it is worked out

  1. kVAr required. kVAr = kW × (tan φ1 − tan φ2), where φ1 and φ2 are the angles of the power factor now and wanted.
  2. Steps. The bank is built in a 1 : 2 : 2 pattern: one small step and the rest twice its size. The smallest step sets how finely the relay can correct. Small banks get up to 6 steps, banks up to 300 kVAr get up to 8, and larger ones up to 12.
  3. Detuned reactors. With 7 % reactors the capacitor voltage rises to 415 ÷ 0.93 = 446 V, so 480 V capacitors are chosen. The capacitor for each step is rated so that the step delivers its kVAr at 415 V.
  4. Current. I = kVAr × 1000 ÷ (1.732 × 415). The incomer and the busbar are sized for 1.5 times this.
  5. Relay. The next standard relay with at least as many stages as steps.

A worked example

A plant runs at 500 kW with a power factor of 0.80. The target is 0.98.

tan φ1 = 0.750, tan φ2 = 0.203
kVAr required = 500 × (0.750 − 0.203) = 273.5 kVAr
Bank = 1 × 25 + 5 × 50 = 275 kVAr in 6 steps
25 kVAr step: capacitor 31.1 kVAr at 480 V; 50 kVAr step: 62.2 kVAr at 480 V
Capacitor current = 275 × 1000 ÷ (1.732 × 415) = 383 A; incomer and busbar for 574 A
Relay: 6 stage

Before you order

  • The calculator assumes a 415 V, 50 Hz system and 7 % reactors. Other systems need their own figures.
  • Where drives or furnaces make up much of the load, check the harmonic levels. A plain capacitor bank can resonate with the transformer.
  • Fast-changing loads, such as welding or cranes, need thyristor switching in place of contactors.

The guide to APFC panel sizing explains each of these, with a table of multipliers for common power factors.

Questions people ask

Which load should I use, connected or running?

The running load in kW at the time the power factor is poor. Using the connected load of the whole plant gives a bank that is too large.

Why does the capacitor rating look bigger than the step?

Behind a 7 % reactor the capacitor sees a higher voltage, so a capacitor of a higher voltage rating is used. Its kVAr is stated at that higher voltage. At 415 V, in series with the reactor, it delivers the step shown.

Why is the incomer sized for 1.5 times the capacitor current?

Capacitors may carry more than their rated current because of harmonics and tolerance on capacitance, so the switchgear and busbar are rated above the nominal current.

Should I aim for a power factor of 1.0?

Most plants aim for 0.98 to 0.99. Going to 1.0 needs much more kVAr for little gain and risks a leading power factor at light load.