What separation is for
Inside a panel, busbars, feeders and cable terminals can share one space or be divided by barriers and partitions. IEC 61439-2 groups the ways of dividing them into forms, from Form 1 to Form 4. In India the same standard is published as IS/IEC 61439-2.
The standard gives separation two purposes:
- to protect a person working on one unit from touching live parts of the next one, and
- to stop solid objects, such as a dropped tool or a loose wire end, passing from one unit to the next.
The form is agreed between the user and the panel builder. It is a choice, not a ranking of quality.
The seven forms in one table
| Form | Busbars and feeders | Feeder and feeder | Outgoing terminals |
|---|---|---|---|
| 1 | Not separated | Not separated | Not separated |
| 2a | Separated | Not separated | Not separated from the busbars |
| 2b | Separated | Not separated | Separated from the busbars |
| 3a | Separated | Separated | Separated from the feeders, not from each other, and not from the busbars |
| 3b | Separated | Separated | Separated from the feeders and from the busbars, but not from each other |
| 4a | Separated | Separated | Each feeder's terminals are in the same compartment as that feeder |
| 4b | Separated | Separated | Each feeder's terminals are in their own enclosed space, apart from the feeder and from other terminals |
"Feeder" here is what the standard calls a functional unit: the breaker or starter of one circuit with its control gear.
Each form in plain words
Form 1
One open space behind the doors. Used for small distribution boards and simple panels where the whole board is switched off for any work.
Form 2
The busbars are behind a barrier and the feeders share one space. It keeps hands away from the busbars but not from the neighbouring feeder. It is used in distribution boards and some small PCCs.
Form 3
Every feeder sits in its own compartment. The outgoing terminals are taken to a common cable alley. In Form 3b that alley is separated from the busbars, which is why 3b is the usual choice for MCCs: a feeder can be opened without exposing its neighbours or the busbars.
Form 4
As Form 3, and each feeder's terminals are also separated from every other feeder's terminals. In 4a they sit inside the feeder's own compartment. In 4b they have a separate enclosed box, usually in the cable alley. Form 4b lets one feeder be cabled while the others stay in service.
What the form does to the price
Each step up adds material and time, and reduces how much fits in a section.
- Sheet steel. More partitions, shrouds and terminal boxes.
- Width. Separate cable alleys and terminal compartments make sections wider or more numerous. A longer panel also needs more main busbar.
- Assembly time. More parts to fit, and more links between each feeder and its terminals.
- Heat. Closed compartments cool less well, so the busbars and components may need a larger size.
A panel priced for Form 3b and built to Form 4b loses money. A panel priced for Form 4b when the client meant 3b loses the order. Settle the form before the price.
Questions to ask before you price
- Does the specification state the form and the sub-type, a or b? "Form 4" alone is not enough.
- Does the incomer need the same form as the feeders?
- Are the partitions to be metal, or may they be insulating material?
- Is the cable entry from the top or the bottom, and is there room for the cable alley on that side?
- Is there a separate requirement for internal arc tests? That is not covered by the form.
The definitions follow IEC 61439-2 (IS/IEC 61439-2), clause 8.101 and its table of forms. Always read the standard itself for a contract.
Questions people ask
Is Form 4 safer than Form 3?
It gives more separation between a feeder's terminals and its neighbours, which helps when one feeder is worked on while others stay live. It is not a rating for arc faults. Internal arc performance is a separate matter with its own tests.
What is the difference between Form 3b and Form 4b?
In Form 3b the outgoing terminals of all feeders share a common cable alley that is separated from the busbars. In Form 4b each feeder's terminals have their own enclosed space, separate from the other feeders' terminals as well.
Which form is usual for an MCC in India?
Form 3b is the most common request for MCCs and PCCs in industrial plants. Form 4b is asked for in process plants where a feeder must be cabled or maintained with its neighbours live.
Does a non-compartmentalised panel have a form?
Yes, Form 1. There is no internal separation, although the panel still has its enclosure and its IP rating.