Coming nextPrakriya: a PLC and SCADA program generator with a batch optimiser.Join the waitlist →
BIRADAR PANELPRO
Guide · panel design

Fault level at an LT panel: from transformer kVA to kA

Every breaker and busbar in a panel must stand the largest current the supply can push into a fault. The sum takes one minute once you know the transformer's rating and impedance.

Why the fault level matters

When a fault happens, the only things that limit the current are the impedances between the source and the fault. Close to a transformer that is very little, and the current is many times the full-load current. The panel has to survive it:

  • each breaker must be able to break it,
  • the busbars and their supports must stand its force, and
  • the busbars must carry it for the stated time, usually one second, without overheating.

Rate the panel too low and it is unsafe. Rate it too high and you pay for breakers and bracing you do not need.

The sum

For a panel fed by one transformer:

Full-load current I = kVA × 1000 ÷ (1.732 × V)
Fault level Ik = 1.05 × I ÷ (%Z ÷ 100)

%Z is the transformer's impedance from its nameplate. The factor 1.05 is the voltage factor of IEC 60909 for the largest fault current in a low-voltage system. Leave it out and you get the round figure many people carry in their heads, which is about 5 % lower.

Worked example

A 1000 kVA transformer with 5 % impedance, feeding a 415 V panel:

I = 1000 × 1000 ÷ (1.732 × 415) = 1391 A
Ik = 1.05 × 1391 ÷ 0.05 = 29.2 kA
Next standard rating = 35 kA

Table for common transformers

415 V, one transformer, worked by the sum above. The impedances are typical values. Use the nameplate figure for a real job.

Transformer%ZFull-load currentFault levelPeakRating to ask for
250 kVA4.5348 A8.1 kA17 kA16 kA*
315 kVA4.5438 A10.2 kA21 kA16 kA
500 kVA4.5696 A16.2 kA34 kA20 kA
630 kVA4.5876 A20.5 kA43 kA25 kA
800 kVA51113 A23.4 kA53 kA35 kA*
1000 kVA51391 A29.2 kA67 kA35 kA
1250 kVA51739 A36.5 kA83 kA50 kA
1600 kVA6.252226 A37.4 kA85 kA50 kA
2000 kVA6.252782 A46.7 kA112 kA65 kA*
2500 kVA6.253478 A58.4 kA140 kA65 kA

* Here the r.m.s. value fits the rating below, and it is the peak that asks for the next one. See the section on the peak.

What adds to it

Running motors

For the first cycles of a fault, running motors feed current back into it. A simple and accepted allowance is four times the running current of the motors.

1600 kVA at 6.25 % = 37.4 kA
400 kW of running motors adds about 2.9 kA
Total = 40.2 kA, still within a 50 kA panel

A second source

If a generator or a second transformer can feed the same busbar at the same time, add the currents. A generator is worked the same way, using its sub-transient reactance Xd'' in place of %Z.

2000 kVA at 6.25 % = 46.7 kA
1010 kVA generator, Xd'' 12 % = 12.3 kA
In parallel = 59.0 kA, which needs a 65 kA panel

If the two can never be connected together, because of an interlocked changeover, take the larger one alone.

What brings it down

The sum above assumes an infinitely strong grid and no cable between the transformer and the panel. Both assumptions make the answer too high, which is the safe side.

  • The grid. The real supply has its own impedance, which lowers the fault level a little.
  • Cables and bus ducts. Every metre adds impedance. The effect is small on a short bus duct and large on a long, small cable.

When the simple sum lands just above a standard rating, a closer calculation with these included may bring it below. That is worth doing before pricing a panel one rating higher.

The peak, and the factor n

A fault current is not symmetrical at first. Its first peak is higher than √2 times the r.m.s. value, by an amount that depends on the X/R ratio of the circuit. The busbar supports must stand the force of that peak.

IEC 61439-1 links the two with a factor n. A panel rated for a given r.m.s. current is taken to stand a peak of n times that current.

R.m.s. short-circuit currentFactor n
Up to 5 kA1.5
Above 5 and up to 10 kA1.7
Above 10 and up to 20 kA2.0
Above 20 and up to 50 kA2.1
Above 50 kA2.2

A 50 kA panel therefore stands a peak of 105 kA. A large transformer has a high X/R ratio, and its calculated peak can pass that figure even when the r.m.s. value is below 50 kA. The 2000 kVA row in the table is such a case. Either take the next rating, or work the peak again with the transformer's real X/R ratio and the impedance of the connection.

Do it in a minute

The fault level calculator does all of this from the kVA and the impedance, with a generator and motors if you have them. In the PanelPro application the same check runs on every estimate and compares the result with each breaker's breaking capacity.

The method is that of IEC 60909 in simplified form, with the peak factors of IEC 61439-1, Table 7. For large or unusual systems, have a fault study made.

Questions people ask

Is 50 kA always enough?

No. It covers a single transformer up to about 1600 kVA at 6.25 % impedance by this method. Larger transformers, or two sources in parallel, can go above it.

Why not rate every panel at 65 kA to be safe?

Because every breaker in the panel must then break 65 kA, and the busbar supports must stand the peak that goes with it. The price rises for no gain if the transformer cannot deliver that current.

Does the fault level fall along a cable?

Yes. Cable impedance lowers it, and quickly on small cables. A sub-distribution board far from the main panel often needs a much lower rating than the main panel does.

What does '50 kA for 1 second' mean?

The panel can carry 50 kA r.m.s. for one second without damage, and stand the peak that goes with it. The breakers must also be able to break 50 kA.