How it is worked out
- Spare. The spare percentage is added to each type of I/O and rounded up.
- Platform. The smallest platform that carries the points is chosen: Micro800 for a small machine, CompactLogix 5380 for most plants, and ControlLogix 5580 where the count is large or redundancy is asked for.
- Modules. Each type is divided by the points of its module and rounded up, for example 16 points for a digital module and 8 for an analog one.
- Racks. Modules are placed beside the controller first, as many as fit on the rail of an 800 mm section. The rest go on remote EtherNet/IP adapters.
- Controller. The smallest controller with enough memory and enough adapter connections.
A worked example
96 digital inputs, 48 digital outputs, 24 analog inputs, 8 analog outputs and 8 RTD inputs, with 20 % spare.
Platform = CompactLogix 5380, controller 5069-L310ER
Modules = 8 × 5069-IB16, 4 × 5069-OB16, 4 × 5069-IF8, 2 × 5069-OF8, 3 × 5069-IY4
Installed points = 252
Racks = 8 modules beside the controller, 13 on one 5069-AEN2TR adapter
What comes after the modules
The module list is the start of a PLC panel, not the end of it. The 24 V DC supplies, the Ethernet switch, interposing relays, fuses and terminals, the panel sections and the wiring all follow from it. In the PanelPro application that is one step: the I/O count becomes the whole panel, with its drawings and its price.
Writing the program for those modules is the next job. Prakriya, our PLC and SCADA program generator, is in development for it.
Allen-Bradley, Micro800, CompactLogix and ControlLogix are trademarks of Rockwell Automation, Inc. This calculator is independent and is not affiliated with or endorsed by Rockwell Automation.
Questions people ask
How much spare I/O should I keep?
Many specifications ask for 20 % installed spare of each type. If yours gives a figure, use it. The calculator adds the spare to each type before it counts modules.
Why does it choose a bigger controller than the I/O count needs?
The controller must also carry the number of remote I/O adapters and have memory for the program. Either can push the choice up one size.
When does it choose redundant controllers?
Only when you tick the box. Redundancy changes the platform to ControlLogix with remote I/O, because the I/O must be shared by both controllers.
Are the catalogue numbers final?
They are a first selection for an estimate. Confirm the numbers, the firmware and the accessories with your Rockwell Automation distributor before you order.